Unexpected ESXi 8.x host shutdown experienced on HPE DL360 Gen11
search cancel

Unexpected ESXi 8.x host shutdown experienced on HPE DL360 Gen11

book

Article ID: 440473

calendar_today

Updated On:

Products

VMware vSphere ESXi

Issue/Introduction

An HPE DL360 Gen11 host installed with HPE Vendor Add-on running ESXi 8.x abruptly powers off. The following symptoms are observed:

  • No Purple Diagnostic Screen (PSOD) is observed on the console.
  • No core dump (vmkernel-zdump) is generated.
  • In the ESXi logs, such as /var/run/log/vmkernel.log, the logging stops abruptly without indicating any specific error or panic message.
  • Additionally, searching various system logs such as /var/run/log/hostd.log or /var/run/log/vmkernel.log for "shutdown" or "thermal" do not provide any information about the event.

Environment

ESXi 8.x on HPE Server Hardware

Cause

By viewing the /var/run/log/syslog.log file, references to Overheating and Insufficient Cooling can be found logged by the HPE Agentless Management Service, ultimately leading to the host shutdown:

yyyy-mm-ddTxx:xx:xx.xxxZ Al(9) smadv[2104335]: System will shutdown in 60 seconds due to Insufficient Cooling.
yyyy-mm-ddTxx:xx:xx.xxxZ In(14) smadv[9899770]: Shutdown timer started.
yyyy-mm-ddTxx:xx:xx.xxxZ Al(9) smadv[2104335]: WARNING: System Overheating (Temperature Sensor 1, Location Ambient, Temperature 43)
yyyy-mm-ddTxx:xx:xx.xxxZ Al(9) smadv[2104335]: CRITICAL: Automatic Operating System Shutdown Initiated Due to Overheat Condition
yyyy-mm-ddTxx:xx:xx.xxxZ Al(9) smadv[2104335]: NOTICE: System Overheating (Temperature Sensor 1, Location Ambient, Temperature 43) has been repaired
yyyy-mm-ddTxx:xx:xx.xxxZ In(14) smadv[2104335]: Shutdown due to Insufficient Cooling has been Aborted.
yyyy-mm-ddTxx:xx:xx.xxxZ In(14) smadv[2104335]: Terminating Shutdown timer ( PID [9899770])...
yyyy-mm-ddTxx:xx:xx.xxxZ Al(9) smadv[2104335]: NOTICE: Automatic Operating System Shutdown Due to Overheat Aborted
yyyy-mm-ddTxx:xx:xx.xxxZ Al(9) smadv[2104335]: NOTICE: Automatic Operating System Shutdown Initiated Due to Overheat Condition has been repaired
yyyy-mm-ddTxx:xx:xx.xxxZ Al(9) smadv[2104335]: System will shutdown in 60 seconds due to Insufficient Cooling.
yyyy-mm-ddTxx:xx:xx.xxxZ In(14) smadv[9899808]: Shutdown timer started.
yyyy-mm-ddTxx:xx:xx.xxxZ In(14) smadv[2104335]: Shutdown due to Insufficient Cooling has been Aborted.
yyyy-mm-ddTxx:xx:xx.xxxZ In(14) smadv[2104335]: Terminating Shutdown timer ( PID [9899808])...
yyyy-mm-ddTxx:xx:xx.xxxZ Al(9) smadv[2104335]: System will shutdown in 60 seconds due to Insufficient Cooling.
yyyy-mm-ddTxx:xx:xx.xxxZ In(14) smadv[9899913]: Shutdown timer started.
yyyy-mm-ddTxx:xx:xx.xxxZ No(13) VMware.shutdown.[9900146]:  Stopping VMs

Additionally, there may be additional evidence in the host Intelligent Platform Management Interface (IMPI) System Event Log (SEL):

  ------- ------------------- ------------------------------ ------------------------------------------------
   Record When                Sensor                         Message
  ------- ------------------- ------------------------------ ------------------------------------------------
      188 yyyy-mm-ddTxx:xx:xx 162 - Other 1 01-Inlet Ambient Assert + Temperature Upper Critical going high
      187 yyyy-mm-ddTxx:xx:xx 162 - Other 1 01-Inlet Ambient Assert + Temperature Upper Critical going high

Resolution

Engage your Hardware Vendor and/or your physical infrastructure/datacenter team to investigate the server location for proper airflow and cooling.

Additional Information

Unexpected ESXi host reboot with Processor Transition to Non-recoverable event in IPMI SEL and no PSOD