An HPE DL360 Gen11 host installed with HPE Vendor Add-on running ESXi 8.x abruptly powers off. The following symptoms are observed:
/var/run/log/vmkernel.log, the logging stops abruptly without indicating any specific error or panic message./var/run/log/hostd.log or /var/run/log/vmkernel.log for "shutdown" or "thermal" do not provide any information about the event.ESXi 8.x on HPE Server Hardware
By viewing the /var/run/log/syslog.log file, references to Overheating and Insufficient Cooling can be found logged by the HPE Agentless Management Service, ultimately leading to the host shutdown:
yyyy-mm-ddTxx:xx:xx.xxxZ Al(9) smadv[2104335]: System will shutdown in 60 seconds due to Insufficient Cooling.yyyy-mm-ddTxx:xx:xx.xxxZ In(14) smadv[9899770]: Shutdown timer started.yyyy-mm-ddTxx:xx:xx.xxxZ Al(9) smadv[2104335]: WARNING: System Overheating (Temperature Sensor 1, Location Ambient, Temperature 43)yyyy-mm-ddTxx:xx:xx.xxxZ Al(9) smadv[2104335]: CRITICAL: Automatic Operating System Shutdown Initiated Due to Overheat Conditionyyyy-mm-ddTxx:xx:xx.xxxZ Al(9) smadv[2104335]: NOTICE: System Overheating (Temperature Sensor 1, Location Ambient, Temperature 43) has been repairedyyyy-mm-ddTxx:xx:xx.xxxZ In(14) smadv[2104335]: Shutdown due to Insufficient Cooling has been Aborted.yyyy-mm-ddTxx:xx:xx.xxxZ In(14) smadv[2104335]: Terminating Shutdown timer ( PID [9899770])...yyyy-mm-ddTxx:xx:xx.xxxZ Al(9) smadv[2104335]: NOTICE: Automatic Operating System Shutdown Due to Overheat Abortedyyyy-mm-ddTxx:xx:xx.xxxZ Al(9) smadv[2104335]: NOTICE: Automatic Operating System Shutdown Initiated Due to Overheat Condition has been repairedyyyy-mm-ddTxx:xx:xx.xxxZ Al(9) smadv[2104335]: System will shutdown in 60 seconds due to Insufficient Cooling.yyyy-mm-ddTxx:xx:xx.xxxZ In(14) smadv[9899808]: Shutdown timer started.yyyy-mm-ddTxx:xx:xx.xxxZ In(14) smadv[2104335]: Shutdown due to Insufficient Cooling has been Aborted.yyyy-mm-ddTxx:xx:xx.xxxZ In(14) smadv[2104335]: Terminating Shutdown timer ( PID [9899808])...yyyy-mm-ddTxx:xx:xx.xxxZ Al(9) smadv[2104335]: System will shutdown in 60 seconds due to Insufficient Cooling.yyyy-mm-ddTxx:xx:xx.xxxZ In(14) smadv[9899913]: Shutdown timer started.yyyy-mm-ddTxx:xx:xx.xxxZ No(13) VMware.shutdown.[9900146]: Stopping VMs
Additionally, there may be additional evidence in the host Intelligent Platform Management Interface (IMPI) System Event Log (SEL):
------- ------------------- ------------------------------ ------------------------------------------------ Record When Sensor Message ------- ------------------- ------------------------------ ------------------------------------------------ 188 yyyy-mm-ddTxx:xx:xx 162 - Other 1 01-Inlet Ambient Assert + Temperature Upper Critical going high 187 yyyy-mm-ddTxx:xx:xx 162 - Other 1 01-Inlet Ambient Assert + Temperature Upper Critical going high
Engage your Hardware Vendor and/or your physical infrastructure/datacenter team to investigate the server location for proper airflow and cooling.