2015-09-10 03:13:54,327 [main] ERROR init() failed 2015-09-10 03:13:54,327 [main] ERROR (90) Configuration error, No value found for key resources/null/name
Environment
Release: Component: CAUIM
Cause
The "null" resource in the <resources> section of the dcim.cfg file is invalid.
This looks like the following in the dcim.cfg file:
<resources> <null> active = false </null> </resources>
Resolution
To delete this, open the dcim Raw Configure GUI, expand the resources folder in the left-hand pane, select the null folder under the resources folder, then select the "Delete Section" button on the left.
<Please see attached file for image>
Apply the change and restart the dcim probe.? This should clear the PPM-023 error when trying to configure the probe.