UIM - Logmon Exit Code Monitoring alarms are Not cleared

book

Article ID: 220430

calendar_today

Updated On:

Products

DX Infrastructure Management

Issue/Introduction

In logmon 4.11 there is an option to monitor Exit Code and set a Threshold for it. 

Alarms are received correctly, however, when the condition is no longer met, a Clear alarm is not sent by the logmon probe. 

Cause

Logmon probe limitation.

Environment

Release : 20.3

Component : UIM LOGMON

Resolution

A new version of the probe resolves this problem. Logmon 4.11_T4.

Starting with this version, the logmon probe will send a clear alarm automatically, without any added config changes, if the threshold defined for the EXIT CODE is no longer braching. 